LFN -P series fluorescent light fittings are normally used in the chemical and petrochemical plants, off-shore platforms, refineries and any other industry where hazardous atmospheres (gas and combustible dust) are potentially present. The LFN -P range of Zone 2 Lighting has been designed to meet the main requirements of illumination of working areas.
LFN - P Explosion proof Fluorescent Light Fitting | ||||||||||
---|---|---|---|---|---|---|---|---|---|---|
product | overall dimensions and weight | fixing dimensions | electrical data | |||||||
A | B | C | kg | b | ∅ | lampholder | power | voltage | ||
![]() |
LFN 114P | 698 | 222 | 145 | 4.9 | 400 | M8 | G5 bi-pin | 1 x 14 W | AC220-240V 50/60Hz |
LFN 118P | 698 | 222 | 145 | 4.9 | 400 | M8 | G13 bi-pin | 1 x 18 W |
|
|
LFN 128P | 1310 | 222 | 145 | 7.8 | 800 | M8 | G5 bi-pin | 1 x 28 W |
|
|
LFN 136P | 1310 | 222 | 145 | 7.8 | 800 | M8 | G13 bi-pin | 1 x 36 W |
|
|
LFN 214P | 698 | 222 | 145 | 5.0 | 400 | M8 | G5 bi-pin | 2 x 14 W |
|
|
LFN 218P | 698 | 222 | 145 | 5.0 | 400 | M8 | G13 bi-pin | 2 x 18 W |
|
|
LFN 228P | 1310 | 222 | 145 | 7.9 | 800 | M8 | G5 bi-pin | 2 x 28 W |
|
|
LFN 236P | 1310 | 222 | 145 | 7.9 | 800 | M8 | G13 bi-pin | 2 x 36 W | AC220-240V 50/60Hz |
The LFN -P series fluorescent lighting fixture are available with two different bodies suitable for installation of single or double fluorescent tube to satisfy every illumination requirements inside hazardous areas classified as Zone 2 and /or Zone 22. The internal wiring is designed to allow any combination of loop-in loop-out installation. The light fitting can be installed using different mounting types as described in dedicated section of this catalogue.
The materials used to manufacture the LFN-P series have been studied to grant the maximum protection against the highly corrosive agents present in these industries:
• the body in glass fiber reinforced polyester (GRP), provides a very high mechanical strength together with a good resistance against the UV ray effects;
• the transparent diffuser in UV ray resistance polycarbonate has a self-extinguishing property according to Standard UL 94;
• the gasket on cover grants an IP66 protection level ;
• the closing system in one single spot, apart from facilitating greatly the maintenance operations, is itself a guarantee of first-rate holding system since it provides a constant pressure of seals over all the perimeter of the diffuser ;
• the internal electrical components are fully sealed to prevent any corrosive action that could cause electrical faults;
• the body has two cable entries M25x1.5 on one side and one cable entry M25x1.5 on the opposite side so to allow any loop-in loop-out installation. On request it’s possible to have two cable entries M25x1.5 on both sides;
• all the light fittings are equipped, as standard, with one cable gland and two stopping plugs in polyamide, Atex certified. Other materials or combinations are available as option;
• two kinds of lampholder: G13 for traditional T8 fluorescent tubes and G5 for new generation of T5 fluorescent tubes;
• electronic ballast, equipped with some self-protective functions, works with a multirange voltage and has a two-supply circuit design so to continue to energize one fluorescent tube in case the second one is faulty;
certificate number: IECEx CML 17.0099X CML 17 ATEX 4183X marking:
Ex II 3GD Ex d mb nA IIC T4 Gc Ex t IIIC T80°C Db
ambient temperature: -25°C +50°C
degree of protection: IP66 conformity:
Directive ATEX 2014/34/EU
standards: IEC-EN60079-0 / IEC-EN60079-1 / IEC-EN60079-15 IEC-EN60079-18 / IEC-EN60079-31
category: suitable for Zone 2 (gas) and Zone 22 (dust)