Connection Kit
This connection kit is designed for terminating all Raychem BTV, QTVR, XTV, KTV and VPL industrial parallel heating cables to a junction box, whilst maintaining electrical insulation of the heating cable conductors and core.
It is approved for use in hazardous areas.
C25-100
- The core sealing boot does not require a heat gun or torch for the installation (no hot work permit necessary). The noncuring sealant (silicone free) allows easy installation and facilitates maintenance purposes. Two grommets supplied in this kit enable the gland to maintain optimum sealing under various ambient conditions.
- An additional locknut is provided for unthreaded entries.
C25-21
- The sealing of the heating cable core is provided by Raychem heat-shrinkable sleeves. Two grommets supplied in this kit enable the gland to maintain optimum sealing under various ambient conditions.
- An additional locknut is provided for unthreaded entries.
C25-100-METAL
- The braid is directly connected to the metal gland body. The connection kits can be used with metal boxes or plastic boxes with internal earthing plate. They are approved for use in hazardous areas.
- The core sealing boot does not require a heat gun or torch for the installation (no hot work permit necessary). The noncuring sealant (silicone free) allows easy installation and facilitates maintenance purposes.
- The C25-100-METAL kit is designed for use with M25 entries, the C3/4-100-METAL for 3/4” NPT entries.
- A metal locknut is provided for earth bonding in plastic junction boxes.
Product | ||||
---|---|---|---|---|
Thread size | Minimum ambient temperature | Max. exposure temperature (gland) | ||
![]() |
C25-100 | M25 x 1.5 | –50°C | 110°C |
C25-21 | M25 x 1.5 | –55°C | 110°C | |
C25-100-METAL | M25 x 1.5 | –60°C | 180°C |